Skip to main content
- DVP-SS2 series PLCs include one 12-point PLC,
and two 14-point PLCs. A DVP-SS2 series PLC provides various instructions, and
the size of the program memory in it is 8k steps. It is able to connect to all
DVP-S series extension modules, including digital I/O (max. 480 I/O points) and
analog modules (for A/D, D/A conversion and temperature measurement). 4 groups
of high-speed (10kHz) pulse output satisfy all kinds of applications. DVP-SS2
is small in size, and can be install easily. Users do not have to install any
batteries in DVP-SS2 series PLCs. The PLC programs and the latched data are
stored in the flash memories.
- This instruction sheet only provides
introductory information on electrical specifications, general specifications,
installation and wiring. For detailed information on programming and
instructions, please refer to “DVP-SS2 Operation Manual: Programming”. For
information about optional peripherals, please see individual product
instruction sheet enclosed with DVP-SS2.
- This is an OPEN TYPE device and
therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance
staff from operating the device (e.g. key or specific tools are required to
open the enclosure) in case danger and damage on the device may occur.
- DO NOT
connect input AC power supply to any of the I/O terminals; otherwise serious
damage may occur. Check all the wiring again before switching on the power.
Make sure the ground terminal is correctly grounded in order to prevent
electromagnetic interference. DO NOT touch any terminals when the power is
switched on